Skip to Main Content

Please visit and bookmark NEMA’s new website www.makeitelectric.org for the latest news and updates.

Search
Recently Searched
    • Store Image Profile Picture Image
      • Edit Page
      • MyNEMA
      • Settings
      • Log Out
      Store Image Login
      • NEMA
      • Standards
      • Benefits of Vendor Remote Monitoring
        • Store Icon White Profile Picture Image
          • Edit Page
          • MyNEMA
          • Settings
          • Log Out
          Store Image Login
      • About
        • About NEMA
        • Careers
        • NEMA Leadership
        • Board of Directors
        • Programs & Events

          2024 Review

      • Membership
        • NEMA Committees & Coalitions
        • NEMA Academy
        • Product Sections
        • Membership Directory
        • Advocacy
          • Action Center
          • Cybersecurity Council Government Relations Subcommittee
          • Healthcare
          • Economic Impact
          • NEMA Mexico
          • Storm Reconstruction Toolkit
          • Contact Us
          • Energy Policy
          • Infrastructure
          • International Trade
          • NEMA Political Action Committee (PAC)
          • Send me the latest news!
          • Regulatory Comments
          • Environmental Stewardship
          • The Energy Transition
          • Make It American Resource Center
          • Policy Trackers

            Read about NEMA Advocacy Efforts in Washington Watch

        • Intelligence
          • NEMA’s Guide to the Electroindustry
          • Economic Impact
          • electroindustry Business Conditions Index
          • NEMA’s Economic Suite
          • Lamp Indices
          • Send me the latest news!

            Get the Latest Electroindustry Business Conditions Indices

        • Standards
          • All Standards
          • Code Alerts
          • Patent Disclosure Policy
          • Standards Store
          • Send me the latest news!
          • All Standards by Product
          • International Activities
          • Technical Field Representative Program
          • White Papers
          • About NEMA Standards
          • Publicaciones en Español
          • Technical Services
          • Why Standards
          • News & Trends
            • Blog
            • Awards
            • Podcast
            • Advertise with NEMA
            • NEMA News
            • Send me the latest news!
            • DICOM
            • MITA
            • More
              Intelligence
              Standards
              News & Trends
              DICOM
              MITA

            Data saved successfully.

            Data saved successfully.

             
            1. NEMA
            2. Standards
            3. Benefits of Vendor Remote Monitoring
            Standards Publication

            Benefits of Vendor Remote Monitoring

            NEMA SG 80040 2024 | Status: Active | ID: 101068

            Recommendations for remote monitoring and examples in this paper are limited to circuit breakers, switchgear, and load interrupters rated from 1kV–52kV. Given the criticality of these types of equipment, inasmuch as they often represent a single point of failure on branch circuits and even feeders, the value of remote monitoring is enhanced. Further, given the complex operational nature of the mechanisms, there are a myriad of possible causes for reduced performance or equipment failure, many of which share a similar level of probability. Finally, much of the equipment at voltages above 52kV already benefit from remote monitoring, so advocacy related to that class of equipment is not necessary
            Buy

            Published Date: September 9, 2024

            Number of pages: 9

            Staff Contact: Paul Crampton

            Download Standard

            Terms & Conditions
            To display, copy and/or download a copy of the document you have requested, NEMA's permission is subject to the following terms and conditions, which you must agree to by clicking on the "I Accept" button below:

            1. I agree not to alter the publication in any way and agree not to change its electronic format.
            2. I agree not to sell or offer for sale the publication for a price or any other consideration.
            3. I agree not to display the publication on a public website or distribute the publication from a public website.
            4. I acknowledge that the copyright to this document belongs to the National Electrical Manufacturers Association (NEMA), and that said copyright owner may revoke its permission or modify any of the foregoing terms and conditions at any time.
            5. I have read NEMA's  Privacy Policy and voluntarily consent to the collection, storage, and use of my personal data provided to NEMA as described in the Privacy Policy.

            Related Products

            Utility Products & Systems Image

            Utility Products & Systems

            Utility Products & Systems Image

            Utility Products & Systems

            Keywords

            NEMA SG 80040 2024, BENEFITS OF VENDOR REMOTE MONITORING, NEMA SG 80040, REMOTE MONITORING

            Topics

            • Switchgear
            Contact Us

            Ads

            logo
            • Facebook fb-icon
            • Twitter twitter-icon
            • Blog bing-icon
            • YouTube youtube-icon
            • Podcast rss-icon
            • LinkedIn linkedin-icon
            • About
            • Membership
            • Advocacy
            • Intelligence
            • MITA
            • News & Trends
            • Standards
            • Store
            Information
            Contact Us
            Home
            Privacy Policy
            Site Map
            Terms & Conditions
            Quick Links
            Environmental Stewardship
            Field Representative Program
            Find a Manufacturer
            Find a Standard
            High Performance Buildings Initiative
            NEMA Staff Login
            Intelligence Portal
            International Activities
            NEMA Membership Inquiry
            MyNEMA
            NEMA Premium